Control unit

Applications
By continuously monitoring the operational status of the detectors, the control unit ensures that any signs of potential explosions are promptly detected and suppressed.
- 1 zone, stand-alone
- Multi-zone
- CUP0302D-B: Base unit: Master Control Unit (MCU) + max 6 zones (ZCN)
- CUP0302D-E: Extension unit for max 6 zones (ZCN) that
communicates with the base unit. Can be monitored and controlled via the base unit.
Working principle:
Reversed polarity = a polarity change of the different components.
- Used both for interpreting the detectors and for controlling the gas generators.
- Almost completely insensitive to external environmental factors.
Detector
When an activation occurs, the reversed polarity detector inverts.
- The ZCN observes this polarity inversion and provides an activation signal to the firing circuit. A 2 millisecond software filter stabilizes this transition.
Characteristics :
- Power supply: 24 V DC +/- 10% or 110-240 V AC +/-10% 50-60 Hz
- Atmosphere:
- 0°C (32°F) to +50°C (122°F)
- Max. 95% at 20°C (68°F)
- Suitable for ATEX zone 22